Quake's jolts were double nuke plant's design
The magnitude-5.8 earthquake last month in
Virginia caused about twice as much ground shaking as a nearby nuclear
power plant was designed to withstand, according to a preliminary
federal analysis.
Parts of the North Anna Power Station in
Mineral, Va., 11 miles from its epicenter, endured jolts equal to 26%
of the force of gravity (0.26g) from some of the higher-frequency
vibrations unleashed by the quake, said Scott Burnell, spokesman of the Nuclear Regulatory Commission.
An
NRC document says the reactors' containment structure was built to
withstand 12% of the force of gravity (0.12g.) Dominion, the power
company that operates the plant, says parts of the plant can handle up
to 0.18g.
"It's
the things inside the buildings that may have been shaken more than the
design called for," Burnell said, adding that the buildings themselves
appear to have been less affected. He said the analysis is based on a
seismograph reading taken about 30 miles away by the U.S. Geological Survey.
Whatever
the final numbers on shaking or ground motion, the plant withstood the
jolts, Burnell said, indicating there's a "great deal" of safety
margin.
"That margin was certainly enough for North Anna this time," he said.
"Maybe you shouldn't rely on the margin," said Edwin Lyman at the Union of Concerned Scientists, an organization critical of nuclear energy. "The jury is still out," he said, on whether the plant was adequately designed.
The
two reactors at the North Anna plant, which began operation in 1978 and
1980, have remained closed since the Aug. 23 quake. They automatically
shut down after losing off-site power. Backup diesel generators kept
their cores cool until electricity was restored several hours later.
Dan
Stoddard, Dominion's senior vice president of operations, said Friday
that initial readings from the facility's scratch plates and other
monitors indicate its shaking during the quake exceeded its design, but
he declined to give numbers. Dominion officials plan to brief the NRC
today on those findings.
Stoddard said the
quake caused "no significant damage" to the facility, based on
Dominion's ongoing inspections. He said there were some cosmetic cracks
in concrete and floor tiles, and 25 of 27 vertical casks holding
spent-fuel assemblies moved up to 4.5 inches.
"The
plant is safe," he said, adding that all radiology readings have been
normal. He said it will be operational again once inspections are
complete. The NRC sent in an augmented inspection team that's slated to
continue its work through next week.